CU VINTOL 35 NL RD V75 1HM

Description

Description

Standards

  • National
    AS/NZS 5000.1

Application

  • Industrial and commercial applications (predominantly)
  • Some domestic applications
  • For use in various situations to supply the main power from the point of supply (either single or three phase application) to buildings, equipment, eg, switch board to main control cabinet, main between floors and buildings, cable cabinet to motor, etc. Commonly used in Power Authority work.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Sheath colour
Red
Conductor material
Copper
Type of conductor
Circular, stranded
Insulation
PVC
Outer sheath
PVC
Conductor flexibility
Class 2
Conductor shape
Circular
Insulation colour
White
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
35 mm²
Nominal overall diameter
13.0 mm
Gland Size (A2 or A2F)
20
Approximate weight
0.45 kg/m
Neutral conductor section (when smaller)
- mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.524 Ohm/km
Permissible short circuit current conductor 1s
3.9 kA
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Max. conductor temperature in service
75 °C
Packaging
-

Resources

Resources

Current carrying capacities single phase (in Amps) - Single conductor PVC

Copper conductor - Circular stranded - Insulation PVC Aluminum conductor - Circular stranded except 240 mm² Compact circular stranded - Insulation PVC Max. Conductor Temperature 75⁰C
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
35.0 101 0 82 0 80 0 134 0 171 0 153 0 67
Air Spaced from Surface, Unenclosed
Air touching, unenclosed
Air enclosed
Buried direct
Buried in single-way duct
Buried in multi-way duct
Cable surrounded by thermal insulation, unenclosed

Current carrying capacities three phase (in Amps) - Single conductor PVC

Single Conductor PVC (three phase) PVC insulation Unarmoured Sheathed or unsheathed For cables up to and including 0.6/1 kV @ 50 Hz AC.
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
35.0 145 0 136 0 114 0 176 0 154 0 134 0 67
Air Spaced from Surface, Unenclosed
Air touching, unenclosed
Air enclosed
Buried direct
Buried in single-way duct
Buried in multi-way duct
Cable surrounded by thermal insulation, unenclosed

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*