CU VERSOLEX 1x 50

Description

Description

Standards

  • Product
    AS/NZS 1125; AS/NZS 3808; AS/NZS 5000.1
  • 0.6/1kV cables,
  • Flexible X-HF-90 (XLPE) insulated
  • TPE sheathed to AS/NZS5000.1 (Power),
  • Copper conductors (Class 5), 90°C.
  • Submersible up to 500m
  • Used for fixed application.

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Type of conductor
Circula, Flexible, Class 5
Colour
Black
Insulation
X-HF-90
Conductor flexibility
Class 5
Conductor shape
Circular
Outer sheath
TPE
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Maximum diameter of wires
0.41 mm
Nominal overall diameter
14.9 mm
Approximate weight
58.0 kg/100m
Cable length
- m
Neutral conductor section (when smaller)
- mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
- Ohm/km
Inductive reactance at 50Hz - flat touching
- Ohm/km
Inductive reactance at 50Hz - trefoil
- Ohm/km
Insulation resistance at 20°C
- MOhm.km
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
0.386 Ohm/km

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible for fixed application
Maximum Pulling Tension
2.5 kN
Mechanical resistance to impacts
Very good

Usage characteristics

Usage characteristics

U.V resistance
Very good
Minimum Bending Radius during installation
9 (xD)
Bending factor when installed
4 (xD)
Maximum operating temperature
90 °C
Minimum operating temperature
0 °C

Resources

Resources

Documentation

Current carrying capacities single phase (in Amps) - Single Core CU Versolex 90°C

Copper conductor - Circular Flexible stranded conductor Insulation X-HF-90 - Max. Conductor Temperature 90⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
50.0 240 196 184 273 203 203 0
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Buried direct
Buried in multi-way duct
Buried in single-way duct
Cable surrounded by thermal insulation, unenclosed

Current carrying capacities three phase (in Amps) - Single Core CU Versolex 90°C

Copper conductor - Circular Flexible stranded conductor Insulation X-HF-90 Max. Conductor Temperature 90⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
50.0 210 196 158 229 174 174 0
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Buried direct
Buried in multi-way duct
Buried in single-way duct
Cable surrounded by thermal insulation, unenclosed

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close