CU ALSEC RHE-1 FLEX 4X 10+4.0E 110 (Class 5)

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • Installation
    AS/NZS 3013

Construction 

Stranded Copper Conductor, X-HF-110 Insulated, HFS-110-TP Sheathed to AS/NZS 5000.1, 110ºC , Fire Rated to AS/NZS 3013 WS52W.

ALSECURE® Multi core range of Fire Rated cable will maintain circuit integrity and life-saving essential services such as emergency and exit lighting, pumps and fans in the event of a fire.

Other sizes and configurations are available on request subject to minimum order quantities.

Features

  • Stranded copper conductor:
    • 2.5mm2 to 6mm(Class 2) Conductor
    • 10mmto 50mm2 (Class 5) Flexible conductor.
  • Halogen free, low smoke, and flame retardant materials
  • 110ºC rated insulation and sheath
  • Circuit integerity up to 120min under fire conditions. Tested to AS/NZS 3013 designation WS52W.

Benefits

  • Flexibilitiy for fast, easy installation
  • Contributes to the green star rating of your project
  • Safer evacuation and protection of essential safety systems

 

The ALSECURE® product range is suitable for Green Star Buildings as they do not contain PVC.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Outer sheath
HFS-110-TP
Type of conductor
-
With smaller neutral conductor
No
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
10 mm²
Number of cores
4
Approximate weight
80.0 kg/100m
Conductor diameter
- mm
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
21.1 mm

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
- Ohm/km
Inductive reactance at 50Hz
- Ohm/km
Insulation resistance at 20°C
- MOhm.km
Max. DC resistance of the conductor at 20°C
1.91 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Maximum Pulling Tension
2.15 kN

Usage characteristics

Usage characteristics

Fire safety
-
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
127 mm
Minimum Bend Radius - Installed
85 mm
Minimum operating temperature
-25 °C
U.V resistance
Yes

Resources

Resources

Selling & delivery Information

Nexans Fire Safety Offer ALSECURE® Fire Resistant Cables PVC-free Red List Free and Declare Labelled

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close